Water Regulations · 9 min read

Updated 28 May 2026

Expansion Vessels and Sealed System Pressure

Pipe Assassin Technical TeamG3 certified, WRAS approved — 10+ years in UK plumbing & water hygiene

Every sealed plumbing system — sealed central heating, unvented hot water — needs an expansion vessel to absorb the volume increase as water heats. The vessel uses a rubber diaphragm with pre-charged air on one side; as water expands, it pushes the diaphragm and compresses the air. Set the pre-charge right and it works quietly for years; get it wrong, or let the air leak out, and you'll see climbing pressure, a weeping pressure relief valve, or a steady drip from the tundish.

Expansion vessels are the unsexy part of any sealed system but they're where most nuisance failures start. This guide covers what they do, the right pre-charge values, the failure symptoms, and the operating pressures you should see on a healthy system. For the wider context on unvented cylinder safety, read G3 unvented hot water cylinders.

Why expansion has to be absorbed

Water expands as it heats. The numbers look small but the effect is significant in a closed vessel:

Thermal expansion of water in a sealed system
Temperature changeVolume expansionExample — 200 L cylinder
10°C → 60°C~1.7%+3.4 L
10°C → 80°C~2.9%+5.8 L
10°C → 95°C (overheat)~4.0%+8.0 L

No vessel = no system

In a truly sealed system with no expansion provision, the additional volume cannot compress (water is essentially incompressible) and the pressure would rise into the hundreds of bar within seconds of heating. Every safety relief would blow at once. The vessel exists to take that energy and turn it into a small, controlled increase in system pressure.

How the vessel works

Inside the steel shell is a rubber diaphragm dividing the vessel into two chambers:

  • Air side — pre-charged through a Schrader valve (like a car tyre valve) to a known pressure.
  • Water side — connected to the system. As water expands, it pushes the diaphragm and compresses the air on the other side.

For the vessel to actually accept water, the system pressure must exceed the air-side pre-charge. If the pre-charge is set too high, water can't get in and the vessel contributes nothing. If it's set too low, the vessel fills with water at cold fill and has nothing left to absorb on heating. Pre-charge has to match the cold fill pressure of the system.

Setting the pre-charge

Typical expansion vessel pre-charge and operating pressures
System typeTypical pre-chargeCold fill / operating pressure
Sealed central heating (small/medium domestic)1.0 barCold fill 1.0-1.2 bar; hot 1.5-2.0 bar; PRV ~3 bar
Sealed central heating (large / multi-storey)1.5 barCold fill 1.5 bar; hot 2.0-2.5 bar
Unvented hot water cylinder3.0-3.5 barCold mains pressure at inlet group (typically 3.0-3.5 bar after reducing valve)
Commercial pressurisation setVariableSet per design — match cold static pressure at the vessel

The pre-charge is always set with the vessel isolated and depressurised on the water side. Trying to "top up" a vessel through its valve while it's still full of water reads garbage and achieves nothing. On an unvented cylinder service, isolating, draining to the vessel, checking and resetting pre-charge is one of the standard annual jobs.

How vessels fail

Two main failure modes:

  • Lost air charge — slow leak through the Schrader valve or diaphragm. The vessel fills with water at cold and has no capacity to absorb expansion. Most common.
  • Ruptured diaphragm — air and water mix. Pressing the Schrader valve releases water rather than air; the vessel is dead and needs replacing.

Climbing pressure or a weeping PRV? We'll diagnose it on the day.

07956 645 527

Enfield-based, 24/7. G3 certified. WRAS approved. Insured to £5m.

Symptoms of a failed vessel

  1. 1

    Pressure gauge that swings dramatically

    Cold the system reads 1.0-1.2 bar; the moment it heats, it climbs to 2.5, 3.0 bar and the PRV opens. That's the textbook failed-vessel pattern on sealed central heating.

  2. 2

    Visible discharge from the boiler PRV pipe outside

    A small puddle or a drip under the white plastic discharge pipe on the outside wall whenever the boiler runs. Often blamed on the PRV itself; usually the PRV is fine and the vessel behind it has failed.

  3. 3

    Steady drip from the tundish on an unvented cylinder

    Every time the cylinder reheats, you see water trickling through the tundish. Failed expansion vessel (or, on bubble-top designs, a lost bubble) is the first thing to check.

  4. 4

    Repeated need to top up

    If you're refilling a sealed heating system every week and there's no visible leak, the PRV has been quietly venting through a failed vessel.

  5. 5

    Press the Schrader valve and water comes out

    Definitive test for a ruptured diaphragm. Replace the vessel — there's no fix.

Checking a vessel — the quick method

  1. 1

    Note the system pressure cold

    On a sealed heating system, that's the pressure gauge with the boiler off and the system cool. Should be around 1.0-1.2 bar.

  2. 2

    Isolate and depressurise the water side

    On heating: isolate the boiler from the system, drain a small amount via the drain-off. On unvented HW: turn off the cold mains feed, open a hot tap, drain enough to drop pressure to zero at the vessel.

  3. 3

    Check pre-charge via the Schrader valve

    Use a dry-pressure (tyre) gauge. Should match the system cold fill — 1.0 bar heating, 3.0-3.5 bar unvented HW.

  4. 4

    Re-charge if low; replace if water comes out

    Top up with a foot pump or compressed air to the target. If water comes out instead of air, the diaphragm is ruptured — replace the vessel.

  5. 5

    Recommission

    Close drains, refill the system to the right cold pressure, vent radiators, run and check the pressure swing on heating.

Ninja Tip

On an unvented cylinder, never try to "fix" a slow tundish drip by tightening or replacing the safety valve. Nine times out of ten the valve is doing exactly what it should — venting because the expansion vessel can't take the heat-up. Sort the vessel and the drip stops on its own. Get an annual service booked in — see G3 unvented hot water cylinders for the full service routine.

Sizing — quick sanity check

On a sealed central heating system the rule of thumb is that vessel volume should be around 10% of total system water volume for a system filled at 1.0 bar and operating to 80°C. On an unvented cylinder, the manufacturer specifies the vessel — typically about 10-12% of cylinder volume (a 200 L cylinder needs around a 24 L vessel). Undersized vessels behave like failed ones: the system can't absorb expansion and the safety valves end up doing the work.

Frequently Asked Questions

What does an expansion vessel do?

It absorbs the volume increase when water is heated in a sealed system. Water expands about 1.7% from 10°C to 60°C; in a sealed cylinder or heating system that extra volume has nowhere to go and pressure would rise sharply. The vessel has a rubber diaphragm with pre-charged air on one side; as the system heats, water pushes the diaphragm and compresses the air, holding pressure within safe limits.

What pre-charge pressure should an expansion vessel be set to?

On a sealed central heating system, typically 1.0 bar — matching the cold fill pressure. On an unvented hot water cylinder, typically 3.0-3.5 bar — matching the cold mains pressure at the inlet group. The pre-charge is always set with the vessel isolated and depressurised on the water side. Wrong pre-charge is the most common cause of nuisance discharge.

How do I know my expansion vessel has failed?

Three classic signs. On heating: cold pressure sits OK at around 1 bar but climbs to 2.5-3 bar when hot and you see water from the boiler PRV pipe outside. On unvented hot water: a slow steady drip from the tundish when the cylinder is heating. On either: a pressure gauge that's far more sensitive than it should be — small changes in temperature cause big pressure swings.

What pressure should a sealed heating system run at?

Cold fill around 1.0-1.2 bar. Hot operating pressure should rise to about 1.5-2.0 bar. The pressure relief valve typically opens at 3 bar. If your gauge sits at 0.5 bar cold you have a leak or a topping-up issue; if it climbs above 2.5 bar when hot the expansion vessel is failing or undersized.

Guidance only. This article is general information for UK readers, not a substitute for a site-specific assessment by a competent person. Regulations and best practice change — always check the current official guidance and, for compliance work (Legionella risk, unvented cylinders, water regulations), use a suitably qualified professional. Pipe Assassin is an electric-boiler and water-hygiene specialist and is not Gas Safe registered; we do not carry out gas work.

Need a real plumber?

Call Pipe Assassin — 24/7 across London, Herts & Essex

07956 645 527

G3 Certified • WRAS Approved • DBS Checked • Insured to £5m

Pipe Assassin — 24/7 Emergency Cover

Need help with water regulations?

Enfield-based, 24/7. 1hr standard cover across London, Herts & Essex. G3 certified, WRAS approved.

  • G3 Certified
  • WRAS Approved
  • £5m Insured
  • 12,000+ jobs
Pipe Assassin Plumbing 24/7 emergency operator taking a UK callout — hooded ninja with phone

24/7 Emergency Plumbing

Your home is flooding.
We’re already on the way.

Burst pipe, no hot water, drain backed up — rapid response, tight ETA on the call.

07956 645 527